Operation
Operating Manual PSEN sc M 3.0/5.5 08-17
1005387-EN-05
| 113
Remove device from the safety laser scanner arrangement
If a device is removed from a safety laser scanner arrangement while this arrangement is in
a rest state, error message INTF18 is displayed when the arrangement is switched on.
Switch off the arrangement again, deactivate the rest state in the configuration and switch
the arrangement back on.
The master unit displays the error INTF18, the subscriber units are in normal operation.
Now change the structure of the safety laser scanner arrangement.
11.8 Deactivate rest condition
Procedure:
1. Select the Configure zone sets window.
Select Rest condition = Deactivated.
2. After approx. 30 seconds the safety laser scanner is again in normal operation.
The display and the LEDs of the safety laser scanner show normal operation.