5-22
PFC-6006 • 5403559 • REV D • 11/17
Table 10: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Zone Silenceable Y Yes/No All settings allowed
Zone Silence Inhibit Y Yes/No All settings allowed
Option is not allowed
for Canada
Zone Auto Silence Y Yes/No All settings allowed
Zone Auto Unsilence Y Yes/No All settings allowed
Zone Restore Delay Y 0-300 Sec Full range allowed
Zone Latching Y Yes/No All settings allowed
Zone Local Y Yes/No All settings allowed
Zone Output Pattern Y
Constant
ANSI Temp 3
March Code
Double Time
Input Point
Dry Contact Input
Functions
Y
Water Flow, Pull Station,
Supervisory, Tamper, Fire
Drill, Trouble Monitor, General
Alarm, Conventional Smoke,
Conventional Heat
All settings allowed
Applies to all input
points and circuits.
Input Point Supervisory Y Yes/No All settings allowed
NAC Function Y
Potter/AMSECO Sync
Gentex Sync
System Sensor Sync
Wheelock Sync
General Purpose
All settings allowed
Species use of
NAC circuit
On-Board
DACT
Daily Test Call Y Any time of day All settings allowed
Alternates between line
1 and 2 if line 2
is enabled.
E-Mail
E-mail Status
Reports
N
Alarms, Troubles, Supervisory
Test & History
IP-Dialer
IP Based Central
Station Reporting
Y
Alarms, Supervisory,
Trouble & Test Reports
All settings allowed
AUX Function Y
Constant, Resettable, Door
Holder, Door Holder Low
AC Drop
All settings allowed