5-21
PFC-6006 • 5403559 • REV D • 11/17
Section 5: Programming
This section addresses programming options and their parameters, provides an overview of the programming process, and
addresses how to use the two programming methods: (1) the LEARN function, and (2) the remote computer programming
process. The LEARN function allows the addition and removal of remote annunciators.
This section also includes procedures on uploading and downloading conguration data using the panel conguration software.
Please refer to this section to learn how to navigate within the software, access and modify programming settings, such as the
system clock, displaying events, and programming optional remote annunciators or the IP Communicator, if installed.
Programming Options
Table 10: Programming Options
Topic
Feature or
Option
Permitted
in UL (Y/N)
Possible Settings
Setting(s) Permitted
in UL864?
Comment
Misc
Idle LCD
Message
Y Yes/No All settings allowed
Misc Display Events Y
Initial Event
Newest Event
Canadian
Initial Event
Auto display of
rst event
Misc Waterow Delay Y 0-255 Sec 0-90 sec
Misc AC Report Delay Y 0-30 Hours 1-3 Hours For UL864 use 1-3 Hr
Misc
DH Low AC
Dropout Delay
Y
No delay, 15 sec, 1 minute,
5 minute
All settings allowed
Misc Auto Test Time Y Time of Day All settings allowed
Misc
Strobes Active
When Silenced
Y Yes/No All settings allowed
Misc Display AM/PM Y AM/PM, 24 Hour All settings allowed
Misc Time Zone Y 24 Time Zone Selections All settings allowed
Misc DST Enabled Y Yes/No All settings allowed
Misc DST Start Y Month/Day All settings allowed
Misc DST End Y Month/Day All settings allowed
Zone Zone Style Y
Alarm
Supervisory
Auxiliary
Fire Drill
System Alarm
System Supervisory
System Trouble
All settings allowed
To users, installers, authorities having jurisdiction, and other involved
parties:
This product incorporates eld-programmable software. In order for the
product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, certain programming
features or options must be limited to specic values or not used at all as
indicated below.