7-68
PFC-6006 • 5403559 • REV D • 11/17
Appendix D – Compatible Points Table
This section provides a listing of all NAC appliances, two-wire (2-wire) smoke detectors, the built-in DACT and remote
annunciator device compatibilities.
Table 25: Device Compatibilities
Module/Device Compatibilities
NAC Appliances
Refer to Potter document “5403592 NAC Compatibility Document”.
Two-Wire (2-Wire) Smoke Detectors Refer to Appendix E for a complete listing of 2-wire smoke detectors.
On Board DACT
DACT – The on-board DACT transmits in Ademco Contact ID and Security Industries
Association’s Digital Communication Standards (SIA-DCS). Each account may be
congured for Contact ID or SIA-DCS independent of the other account’s setting.
Therefore, some account(s) could be Contact ID and others could be SIA-DCS or vice
versa. Similarly, accounts could be the same reporting type.
Receivers
Silent Knight Model 9500/9800 (Ademco MX8000)
Sur-Gard System III – SG-DRL3 (POTS Line Card)
IP Reporting
Sur-Gard System III – SG-DRL3-IPCA (Network Line Card)
Notes:
1. Where the re alarm transmitter is sharing on-premises communications equipment,
the shared equipment shall be Listed.
2. Secondary power shall be provided for all equipment necessary for the transmission
and reception of alarm, supervisory and trouble signals at the protected premises.
3. Secondary power shall be provided for all equipment necessary for the transmission
and reception of alarm, supervisory and trouble signals at the supervising stations.
4. The connection between the FACP and on-premises communications equipment
shall be limited to 20 feet and enclosed in conduit or equivalently protected against
mechanical injury.
RS-485 Points RA-6075 or RA-6006 – LCD Remote Annunciator