EasyManua.ls Logo

Potter PFC-6006 - Multiple Zones; Mapping Terminology; Zone Types; Styles

Potter PFC-6006
83 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5-47
PFC-6006 • 5403559 • REV D • 11/17
Mapping Terminology
The table below provides mapping terms that may be helpful to you in understanding the mapping concept:
Table 16: Mapping Terminology
Term Denition
Mapping
Creating relationships between points, modules and sensors and dening their behavior.
Zone
A group of points.
Zones may represent a group of points located in a specic physical area at the site.
Example: Zone 1 comprised of all alarm devices for a sprinkler system [i.e., pull station #1, one (1)
water ow device, and one (1) strobe-NAC].
Zones may represent a set of points congured for a specic function; their location may be scattered
throughout the site. This group is a “logical” grouping or zone.
Example: Zone 2 comprised of all points in Zone 1 as described above, plus a 2
nd
pull station located
at end of a hallway and two (2) additional smoke detectors.
Notes:
1. If all input / output points are grouped into one (1) zone, when any input is activated, all outputs
activate.
2. A device or point may be mapped into more than one (1) zone.
Point
Any specic initiating device circuit (IDC) or appliance connected to panel.
Latching
Device will not automatically reset; device must be RESET at the keypad to remove condition.
Non-Latching
Device will automatically reset when trouble and supervisory condition is no longer present.
Zone Types / Styles
You may dene or congure each zone to serve a specic purpose or to create specic output results. For procedures on how to
select Zone styles, refer to the “Conguring Zones” section of this manual. The following zone styles are available:
Table 17: Zone Styles
Zone Description
Alarm
•y Default zone type.
•y Sets system into an Alarm condition when any input is activated.
Supervisory
Used for all Supervisory inputs.
Auxiliary
Used for all “Aux” inputs.
Fire Drill
Comprised of input / output points that will activate when running a Fire Drill.
System Alarm
Used for outputs that will be activated upon any alarm.
System Supervisory
Used for outputs that will be activated upon any supervisory.
System Trouble
Used for outputs that will be activated upon any trouble.

Table of Contents

Other manuals for Potter PFC-6006

Related product manuals