5-51
PFC-6006 • 5403559 • REV D • 11/17
Input Circuit Functions
The IDC's ("Conventional Inputs") default to specic functions as shown in the 2nd table below; however, they may be
recongured and renamed, based on the following conguration functions:
Table 19: Input Circuit Functions
Function Description
Contact Input Pull Station Pull Station Input
Contact Input Water Flow Water Flow Input obeys water ow delay as dened in "General Options".
Contact Input Supervisory Supervisory Input
Contact Input Tamper Tamper Input reports as supervisory.
Contact Input Fire Drill Fire Drill Input activates a re drill.
Contact Input Trouble Monitor Trouble Input creates a trouble condition.
Contact Input Aux Aux Input reports as un-typed alarm.
The six (6) Input or Initiating Device Circuits (IDC) automatically default as follows:
Table 20: Input Circuit's Default Conguration
Input Circuit Default Function
Input 1 Water Flow
Input 2 Smoke Detector
Input 3 Manual Pull
Inputs 4 & 5 Supervisory
Input 6 Valve Tamper