PFC-6006 • 5403559 • REV D • 11/17
Detector Model Identier Base Model Identier
SOC-24V HD-3 HSB-221 HB-54
NS6-221 HB-4
NS4-221 HB-4
NS6-220 HB-3
SOC-24VN HD-3 HSB-221 HB-54
NS6-221 HB-4
NS4-221 HB-4
NS6-220 HB-3
FENWAL (Max. No. Of Detectors Per Zone Is 25)
CPD-7051* I51FE1 2-WIRE FE51A
PSD-7155* P55FE1 2WRLT FE52A
PSD-7156* P56FE1 2WRB FE55A
All of the above Fenwal detectors and bases can be used in any combination.
Retrot Base Adaptor 70-501000-003, Identier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003, and -005).
Duct Housing with Detector Base DH-51, Identier DH22FE5 (for CPD-7051 and PSD-7155 detectors only).
POTTER (Max. No. Of Detectors Per Zone Is 25)
PS-24* HD-3 (HOCHIKI) SB-46 HB-71(HOCHIKI)
HB-54 (HOCHIKI)
SB-93 HB-3 (HOCHIKI)
PS-24H HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)
IS-24* HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)
CPS-24 HD-3 (HOCHIKI) SB-46 HB-4 (HOCHIKI)
SB-93 HB-3 (HOCHIKI)
CPS-24N HD-3 (HOCHIKI) SB-46 HB-4 (HOCHIKI)
SB-93 HB-3 (HOCHIKI)
*UL and ULC Listed.
NOTE: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.