Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board
284 Quantum Scalar i40 and Scalar i80 User’s Guide
d Click Apply
e Click OK.
Note: Restoring the configuration does NOT restore your network
settings.
5 Check the library’s date, time, and time zone settings and
reconfigure if necessary. From the Web client, select Setup > Date
& Time.
6 If you changed the IP address from what it was originally, update
host and other applications that access the library.
7 Save the library configuration. From the Web client, select Tool s >
Save/Restore Configuration. Select Save Configuration and click
Apply. Save the configuration to a known location.
8 It is recommended that you run the Installation and Verification Test
(IVT). From the operator panel, select To ol s > IVT and follow the
instructions. The IVT takes about 30 minutes. If any problems are
detected, the library issues a diagnostic ticket.
9 Package the old SCB in the packaging that shipped with the new
SCB and send the old SCB back to Quantum using the included
return shipping label.
Manually Reconfiguring
the Library
Follow the instructions in this section if you do not have a saved library
configuration.
1 If you had licenses installed on your library, have the license keys
handy so you can install them on the library. If you no longer have
them, you can obtain them at http://www.quantum.com/
licensekeys, or from Quantum Support.
2 When the firmware update is complete, the Setup Wizard displays
on the operator panel screen. The Setup Wizard helps you configure
the date, time, IP address, IPv6 enable/disable, licenses, partitions,
I/E slots, and cleaning slots.