EasyManua.ls Logo

semaphore KINGFISHER PLUS+ - 3.2.5 Module LEDs

semaphore KINGFISHER PLUS+
247 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Kingfisher Plus+ Hardware Manual
3.2.5 Module LEDs
PS-x2 LEDS
PS-22-x
LED
State
Description
OK
ON Module operating normally.
960 ms ON,
80 ms OFF
No communications with RTU Processor Module.
OFF Power off or Module fault.
VIN
ON
Mains present / SMPS running
1,2
.
OFF
Mains not present / SMPS not running.
OVLD
65 ms ON,
450 ms OFF
In Overload Mode. Output voltage is being ramped down (when powered
from Mains).
OFF PS-x2 is not in Overload Mode.
Tx
ON
The PS-x2 is sending data to Processor Module via Backplane.
OFF
No data being sent to Processor Module.
Rx
ON
Any RTU module sends data via Backplane.
OFF
No data being sent by other modules.
BATT (Battery) LEDs
DET
ON
Battery or load or DC source connected to B terminals.
OFF
No battery nor load nor DC source connected to B terminals
3
.
FLT
ON
Battery is slow (float) charging.
OFF
Battery is not in Float Charge mode.
BST
ON
Battery is fast (boost) charging.
10 ms ON,
2.0 s OFF
Boost charge is not possible (either external temperature sensor not
connected or it is faulty or battery temperature is out of -20 °C to +60 °C).
OFF
Battery is not in Boost Charge mode.
Hardware Manual Version 7.16
http://www.servelec-semaphore.com/
Page 41

Table of Contents