Parameter Description
Parameter
Remarks
89 0 0~10
0 Slip compensation is forbidden.
10
The compensation value is 3% of the target
frequency when P.89 = 10.
5.43 The Inverter Model (P.90)
P.90 “The inverter model”
● P.90 is used to show the type and capacity of inverter, and the parameter can only be read.
P.90 =
Input voltage: 1: 220V 1-PHASE
2: 220V 3-PHASE
3: 440V 3-PHASE
Applicable motor capacity: please
refer to the following table
The applicable motor capacity is as following table:
Value (value of the two
capacity (kw)
Value (value of the two
capacity (kw)
4 1.5 14 37
5 2.2 15 45
6 3.7 16 55
7 5.5 17 75
8 7.5 18 90
9 11 19 110
10 15
11 18.5
21 160
12 22
13 30
5.44 Frequency Jump (P.91~P.96)
P.91~P.96 “Frequency jump”
● To avoid system’s mechanical resonance frequency when running the motor, the inverter
provides three sets of jump frequencies, namely, P.91 (the first set), P.92 (the second set),