Parameter Description
Parameters
116
5.33 Brake Selection (P.71)
P.71 Idling braking and linear braking selection”
Parameter Factory setting Setting range Remarks
71 1 0, 1 ---
<Setting>
P.71=0 is now idling braking. The inverter will terminate the output immediately after the
stop sign is pressed, and the motor will be “racing.
ON OFF
Operation
signal
time
Output frequency
(HZ)
The motor idling breaking
P.71=1, it is now linear braking. The output of the inverter will follow the acceleration /
deceleration curve after the stop sign is pressed.
time
Output frequency (Hz)
ON OFF
Operation
signal
Deceleration time
(the time is set by P.8)
linear
braking
5.34 Carrier Frequency (P.72)
P.72 “Carrier frequency”
Parameter Model Factory setting
Setting
range
Remarks
72
Frame AA
Frame A/B
5kHz 1~15 kHz
---
Frame D/E 4kHz 1~9 kHz
Frame F 2kHz 1~9 kHz

Table of Contents