EasyManuals Logo

Shihlin electric SF-GT Series User Manual

Shihlin electric SF-GT Series
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #169 background imageLoading...
Page #169 background image
Parameter Description
Parameters
168
<Setting>
P.294 is the parameter that provides the decrypt function. P.294 will be zero if the
decryption is successful. Use P.295 to set the password. Enter the initial password
into P.294 to decrypt the parameter password and to modify or to set up various
parameters.
P.295 is the parameter for setting up the password. The password has to be greater than 1.
Once the password setup is completed, P.295 will display 1. After deleting the password,
P.295 will display 0.Once the password is set, no parameter can be modified, except P.294.
P.998 and power shutdown have no effect on the password. The parameters can be revised
only after the decryption.
Note: Bring the inverter to the factory for decryption if the password is forgotten.
5.77 Motor Control Mode (P.300 and P.301)
P.300 “Motor control mode selection
P.301 “Motor parameter auto-tuning function selection”
Parameter
Factory
setting
Setting
range
Remarks
300 0 0~4
0 V/F control
1 Close-loop V/F control (VF + PG)
2 General flux vector control
3 Sensorless vector control (SVC)
4 Close-loop vector control (FOC + PG)
301 0 0~4
0 Parameter auto-tuning function with no motor
1
Motor parameter auto-tuning measuring the
running motor
2
Motor parameter auto-tuning measuring the
stopped motor
3 Online auto-tuning function
4
The system inertia auto-tuning measuring in
the mode of closed loop vector control
<Setting>
When P.300=0, no motor parameter auto-tuning function is required for normal V/F curve
operation.
For general magnetic vector control, please set P.300 to 2. The frequency will be altered
due to elevated voltage and increased compensatory motor load.
For executing the motor parameter auto-tuning function, set P.301 to 1 or 2 and press the
forward rotation or the reverse rotation key. During the measuring process, the operation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shihlin electric SF-GT Series and is the answer not in the manual?

Shihlin electric SF-GT Series Specifications

General IconGeneral
BrandShihlin electric
ModelSF-GT Series
CategoryInverter
LanguageEnglish

Related product manuals