Parameter Description
Parameter
Remarks
175 0 0~100% ---
176 30s 0~600s ---
177
0
0, 1, 2
0 Free stop
1 Decelerate and stop
2 Continue to run when the alarm goes off
178 0 0~100% ---
181 40Hz 0~120Hz ---
182 100.0%
0~200.0
%
When the deviation value accumulated with the integral
time, an upper limit for deviation accumulation should be
set. For example, the upper integral limit of frequency is
183 0.5Hz 0~10Hz
When the feedback pressure satisfies the deviation value
for stopping the machine and the set time (in seconds) for
stopping the machine for detection is reached, the
inverter will take the P.183 step to reduce the frequency.
223 0%
100%
Revising the feedback signal to unify the signal range of
inverter’s feedback terminal and actual feedback, so that
the
inverter display in accordance with the feedback
meter.
224 100%
225 20%
0~100%
The target value is set by P.225 when the ten-digit of
P.170 value is 0, and the single-digit is not 0.
241 20ms
0~6000ms
The parameter is the sampling period for feedback signal.
The adjuster computes once every sampling period. The
longer the sampling period, the slower the response.
<Setting>
• The revising instruction of the analog feedback bias pressure and gain pressure:
1.The system default value can be used to revise without connecting with feedback signal,
the default value is as follows:
The feedback of terminal 2-5 The feedback of terminal 4-5 The feedback of terminal 1-5