Parameter Description
● Function of regeneration and avoidance: When the regenerative status is serious, the DC
bus voltage rises and an overvoltage alarm OV may occur. The function is to improve the
output frequency of inverter and decrease the DC bus voltage for avoiding alarm OV when
overvoltage happens(as the following shows).
Parameter Designation
Parameter Specification
P.269
Regeneration
and avoidance
detection
sensitivity at
deceleration
0
0
Regeneration avoidance by bus
voltage change ratio is invalid
1~5
Set sensitivity to detect the bus
voltage change ratio
Setting 1 to 5
Detection sensitivity low to high
P.270
Regeneration
avoidance
compensation
frequency limit
6.00HZ
0~10.00HZ
Set the limit value of frequency
which rises at activation of
regeneration avoidance function.
99999 Frequency limit invalid
(automatic
and avoidance
100.0% 0~200.0%
activation of regeneration
avoidance. When alarm
happens,set a larger value in
P.271. when shock happens,
please set a proper smaller value
in P.271, if the shock still
continue, please set a proper
P.272
( automatic
mode)
Regeneration
and avoidance
I factor
100.0% 0~200.0%
P.271
(manual
mode)
and avoidance
acceleration
10.00HZ/S 0~20.00HZ/S
Set regeneration and avoidance
action speed of Acc/Dec
according to system inertia.
P.272
(manual
mode)
and avoidance
deceleration
10.00HZ/S 0~20.00HZ/S