7.15.2 Connecting a new device in an existing cascade
Overview
If y
ou use an unconfigured device to extend a cascade or to replace a (defective) device
in a cascade, the unconfigured device adopts the configuration for the restart interlock
and external device monitoring from the existing devices.
Approach
1.
Install and wire the device.
2. Set the DIP switches for the beam coding on the receiver of the host system.
3. Switch on the voltage supply.
The device is in configuration mode, the field indicator flashes green.
4. If the restart interlock or external device monitoring was configured for at least one
existing device, the configuration is adopted.
5. Wait until all receivers indicate the correct cascade configuration. In a cascade,
diagnostic LED 2 flashes.
6. Wait approx. 3 s longer.
7. Disconnect the device from the voltage supply.
The device can now be put into operation.
Further topics
"R
eset to factory settings", page 94
"Configuring beam coding", page 96
7.15.3 Connecting preconfigured devices in an existing cascade
If you use a device that may already have been configured to extend a cascade or to
r
eplace a (defective) device in a cascade, reset the device to the factory settings first.
Further topics
"R
eset to factory settings", page 94
"Connecting a new device in an existing cascade", page 108
"Configuring beam coding", page 96
7.16 Status indication on both sides
The OSSD status and the status of the protective field are indicated via LEDs on the
sender and r
eceiver when the following applies:
The sender and receiver are connected to one another in the control cabinet
The sender and receiver are connected to one another via a T-connector
The status information is transferred from the receiver to the sender automatically. A
configuration process is not required.
Further topics
"C
onnection of sender and receiver", page 59
7 C
ONFIGURATION
108
O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK
Subject to change without notice

Table of Contents

Other manuals for SICK deTec4

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK deTec4 and is the answer not in the manual?

SICK deTec4 Specifications

General IconGeneral
BrandSICK
ModeldeTec4
CategorySafety Equipment
LanguageEnglish

Related product manuals