4.3.7.5 Total time for Smart Box Detection
The total time limits the maximum duration for Smart Box Detection to 24 hours, i.e.
Smar
t Box Detection is terminated at the latest when the total time has expired. The
system then changes to the Smart Box Detection Override required state.
The total time for Smart Box Detection is always active.
4.4 Integration in electrical control
Overview
T
his chapter contains important information about integration in the electrical control.
Information about the individual steps for electrical installation of the device: see
"Electrical installation", page 86.
Important information
DANGER
H
azard due to lack of effectiveness of the protective device
In the case of non-compliance, it is possible that the dangerous state of the machine
may not be stopped or not stopped in a timely manner.
b
Make sure that the following control and electrical requirements are met so that
the product can fulfill its protective function.
Requirements for use
The output signals of the protective device must be analyzed by downstream controllers
in such a way that the dangerous state of the machine is ended safely. Depending
on the safety concept, signal evaluation is carried out e.g. with safety relays or with a
safety controller.
It mus
t be possible to electrically influence the control of the machine
The electrical control of the machine must meet the requirements of IEC 60204-1
When using a safety controller, different signal levels of both OSSDs must be
detected depending on applicable national regulations or required reliability of the
safety function. The maximum discrepancy time tolerated by the controller must
be selected according to the application.
The OSSD1 and OSSD2 output signals must not be connected to each other
In the machine controller, the signals of both OSSDs must be processed sepa‐
rately
Figure 30: Dual-channel and isolated connection of OSSD1 and OSSD2