LEDs End cap with
int
egrated
LED
Meaning
OSSD Field Diagnostic LEDs
1 2 3 4 5 6 7 8
O
W
hite
(3 s)
Scanning range
ad
justment is con‐
figured.
O R
ed ÖÖ
Yellow/
green
o o o o o o o o ÖÖ Yel‐
low/green
Reset of the con‐
f
iguration to fac‐
tory settings is acti‐
vated, see "Factory
settings", page 93.
O R
ed Ö
Green
Ö Green
Device is in con‐
f
iguration mode,
see "Configuration
mode", page 95.
When a function
is configured, the
corresponding diag‐
nostic LED flashes.
o LED off. Ö LED flashes. O LED illuminates. Empty cells mean that the LED lights up, flashes, or is off.
After the configuration is displayed, diagnostic LEDs 1, 2, 3 and 4 indicate the align‐
ment q
uality. Additionally, the synchronization status of the topmost and bottommost
beams of the safety light curtain are displayed by means of diagnostic LEDs 5 and 6 as
well as 7 and 8.
If the configuration was changed, the diagnostic LEDs flash white for 3 s upon activa‐
tion.
Once the safety light curtain is aligned and the protective field is clear (field indicator:
flashing yellow or lit up green), the alignment quality display switches off after a certain
period of time.
Table 44: Indication of the alignment quality
LEDs Meaning
Diagnostics LEDs
1 2 3 4 5 6 7 8
o o o o o o o o
Alignment is inadequate, or the protective field is
a
t least partially interrupted. The receiver cannot
synchronize with the sender.
O Blue o o o
At least one beam is synchronized.
Ho
wever, the alignment is inadequate, or the pro‐
tective field is at least partially interrupted.
O Blue O Blue o o
The alignment or the signal strength is still not
suf
ficient for stable availability, or the protective
field is at least partially interrupted.
1)
O Blue O Blue O Blue o
Alignment is good, stable availability.
1)
2)
O Blue O Blue O Blue O Blue
Alignment is very good.
1)
O Blue O Blue
The topmost light beam (far from system plug) is
s
ynchronized.
11 TROUBLESHOOTING
126
O P E R A T I N G I N S T R U C T I O N S | deTec4 8021645/1EB0/2022-04-28 | SICK
Subject to change without notice