Chapter 7 Operating Instructions
M4000 Adv., Adv. A/P, Area
62 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 8010797/PA53/27-06-05
Commissioning
Testing the light path between sender and receiver
Prior to covering each light beam with a test rod, check whether …
the green LED lights up on the M4000 with de-activated internal restart interlock.
the yellow LED lights up on the M4000 with activated internal restart interlock
(“Reset required”).
If this is not the case, ensure that this condition is reached. The test is otherwise
meaningless.
Only M4000 Advanced:
Completely cover each light beam with a test rod that is not transparent to light (at
least 30 mm diameter) at the following positions:
immediately in front of the sender
in the middle between sender and receiver (or between the deflector mirrors)
immediately in front of the receiver
when using deflector mirrors: immediately before and after the deflector
Only M4000 Advanced A/P:
Completely cover each light beam with a test rod that is not transparent to light (at
least 30 mm diameter). Hold the test rod in the following positions with your arm
outstretched:
immediately in front of the M4000 Advanced A/P
in the middle between M4000 Advanced A/P and M4000 Passive or another mirror
deflection (e.g. deflector mirror PSK45)
immediately in front of the M4000 Passive or another mirror deflection (e.g. deflector
mirror PSK45)
when using deflector mirrors between M4000 Advanced A/P and M4000 Passive:
immediately before and after the deflector
Only M4000 Area 60/80:
Use a test rod that is not transparent to light and that has the following diameters:
60 mm for the M4000 Area 60
80 mm for the M4000 Area 80
Guide the test rod along the entire length of the area monitored:
immediately in front of the sender
in the middle between sender and receiver
immediately in front of the receiver
This must produce the following result:
On the receiver for the related multiple light beam safety device only the red LED is
allowed to illuminate and not the green or yellow LED
and
as long as the light beam is interrupted, it must not be possible to initiate the
dangerous state.
Note
AUDIN - 7 bis rue de Tinqueux - 51100 Reims - France - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr

Table of Contents

Other manuals for SICK M4000 Advanced

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK M4000 Advanced and is the answer not in the manual?

SICK M4000 Advanced Specifications

General IconGeneral
TypeMultiple light beam safety device
Enclosure ratingIP65
Supply voltage24 V DC
Safety integrity levelSIL3
Performance levelPL e
Protection RatingIP65
Operating Voltage24 V DC
Number of beams2 to 4 beams
Resolution70 mm
Ambient operating temperature-25 °C ... +55 °C
Angular ResolutionNot applicable
Operating Temperature-25 °C ... +55 °C