Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
MMTR*.DmdVArh
Information Value
Reactive Energy Imp MMTR*.DmdVArh.actVal Measured Value Value
MMTR*.DmdVArh.units.SIUnit 73 VArh
MMTR*.DmdVArh.units.multiplier 3 None
MMTR*.DmdVArh.pulsQty
10
1
None
MMTR*.DmdWh
Information Value
Active Energy Imp MMTR*.DmdWh.actVal Measured Value Value
MMTR*.DmdWh.units.SIUnit 72 Wh
MMTR*.DmdWh.units.multiplier 3 None
MMTR*.DmdWh.pulsQty
10
2
None
MMTR*.SupVArh
Information
Value
Reactive Energy Exp MMTR*.SupVArh.actVal Measured Value Value
MMTR*.SupVArh.units.SIUnit 72 VArh
MMTR*.SupVArh.units.multiplier 3 None
MMTR*.SupVArh.pulsQty
10
3
None
MMTR*.SupWh
Information
Value
Active Energy Imp MMTR*.SupWh.actVal Measured Value Value
MMTR*.SupWh.units.SIUnit 72 Wh
MMTR*.SupWh.units.multiplier 3 None
MMTR*.SupWh.pulsQty
10
4
None
1
Dependant on the Reactive Imp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty.
By default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
2
Dependant on the Active Imp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty. By
default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
3
Dependant on the Reactive Exp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty.
By default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
4
Dependant on the Active Exp Energy Unit setting. The unit of energy is calculated by combining the multiplier and the pulsQty. By
default this is 10
3
⋅ 10 = 10,000 or 10 kVArh.
Device Functionality
3.6 Data Storage
112 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual