CNTLOGGIO1.Health
Information
Device Healthy 0 1
CNTLOGGIO1.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
CNTLOGGIO1.ISCSO1
Information Measurand Value
CB Count To AR Block CntLOGGIO1.ISCSO1.stVal 0 to 10000
Information
CB Count To AR Block Value (0 to 10000)
CntLOGGIO1.ISCSO1.Oper.ctlVal Value (0 to 10000)
CNTLOGGIO1.ISCSO2
Information
Measurand Value
CB Count To AR Block Target CntLOGGIO1.ISCSO2.stVal 0 to 10000
Information
CB Count To AR Block Target Value (0 to 10000)
CntLOGGIO1.ISCSO2.Oper.ctlVal Value (0 to 10000)
CNTLOGGIO1.SPCSO
Information
CB Count To AR Block Target Reached 0 1
CNTLOGGIO1.SPCSO 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value FALSE: 0
TRUE: 1
Information List
Input/Output Matrix
General
Pickup
User Logic Type IEC
60870-5-1
03
DNP3 MODBUS
RTU
79 Out Input
79 In Input
Autoreclose on/off Control Y Y
79 Lockout Input
79 Block Reclose Input
7.3.7
Control Functions
7.3 79 Automatic Reclosing
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 439
C53000-G7040-C014-1, Edition 11.2019