Information
A59VxPTOV*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A59VxPTOV*.Op
Information
Element Operated 0 1
A59VxPTOV*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A59VxPTOV*.Str
Information
Element picked up 0 1
A59VxPTOV*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information List
Input/Output Matrix
General
Pickup
User Logic Type IEC
60870-5-1
03
DNP3 MODBUS
RTU
Inhibit 59Vx-n Inhibit 59Vx-n Input
59Vx-n 59Vx-n Operated Output Y Y Y
59Vx-n
Pickup
59Vx-n Pickup Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.24.7
Protection and Automation Functions
5.24 59Vx Overvoltage Protection – Vx
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 323