Parameter: En Counter Reset Time
Default Setting:
Where En Counter Reset Time elapses without further count increments the count value is reset to
zero.
Settings Example
E1= I1.!I2: Equation 1 = Binary Input 1 AND NOT Binary Input 2 The output of E1 is set to true when the
conditions of the equation are met.
Settings Menu
Configuration > Quicklogic
Parameter Range Default Setting
Quick logic Enabled
Disabled
En Equation Enabled
Disabled
En = 0, 1, 2, 3, 4, 5, 6, 7, 8, 9, ( , ), >,
^, !, ., In, Fn, Ln, On, Vn
En Pickup delay 0 to 14400 s 0 s
En Dropoff delay 0 s
En Counter target 1 to 999 1
En Counter reset mode Off, Single Shot, Multi Shot Off
En Counter reset time 0 to 14400 s 0 s
IEC 61850 Functional Information Mapping
EGGIO1.Mod
Information
Reset Device x
EGGIO1.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
EGGIO1.Health
Information
Device Healthy 0 1
EGGIO1.Health.stVal 3 1
3.8.5
3.8.6
Device Functionality
3.8 Quick Logic
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 133
C53000-G7040-C014-1, Edition 11.2019