Settings Menu
Functions > Function Config
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
81HB2 2nd Harmonic Enabled
Disabled
Disabled
Functions > Protection > 81HB2 > Gn 81HB2-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Setting 0.1 to 0.5 ⋅ I, Δ 0.01 ⋅ I 0.2 ⋅ I
Bias Cross
Phase
Sum
Cross
IEC 61850 Functional Information Mapping
A81HB2PHAR*.Mod
Information
81HB2 2nd Harmonic Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A81HB2PHAR*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A81HB2PHAR*.Health
Information
Device Healthy 0 1
A81HB2PHAR*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
6.6.5
6.6.6
Supervision Functions
6.6 81HB2 Inrush Current Detection
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 395
C53000-G7040-C014-1, Edition 11.2019