Information
I_RFLT.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
I_RFLT.Health
Information
Device Healthy 0 1
I_RFLT.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
I_RFLT.A
Information
Value
Ia (Ia =) I_RFLT.A.phsA.cVal.mag.f Measured Value Value
I_RFLT.A.phsA.units.SIunit 5 A
I_RFLT.A.phsA.units.multiplier 0 1
Information Value
Ib (Ib =) I_RFLT.A.phsB.cVal.mag.f Measured Value Value
I_RFLT.A.phsB.units.SIunit 5 A
I_RFLT.A.phsB.units.multiplier 0 1
Information Value
Ic (Ic =) I_RFLT.A.phsC.cVal.mag.f Measured Value Value
I_RFLT.A.phsC.units.SIunit 5 A
I_RFLT.A.phsC.units.multiplier 0 1
Information Value
Ineut (Ig =) I_RFLT.A.neut.cVal.mag.f Measured Value Value
I_RFLT.A.neut.units.SIunit 5 A
I_RFLT.A.neut.units.multiplier 0 1
Energy Storage
The energy measurement storage function corresponds to the logical node MMTR* in IEC 61850.
The energy is displayed and reported as a count value x the Energy Storage > Active/Reactive
Exp/Imp Energy Unit parameter.
The measured power is continuously integrated (over a 1-second window) to produce 4 energy quantities:
3.6.4
Device Functionality
3.6 Data Storage
118 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019