Siemens 7SR51 - IEC 61850 Functional Information Mapping

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions > Protection > 51G > Gn 51G-n
Parameter Setting Options Settings
Default Gn1 Gn2 Gn3 Gn4
Delay (DTL) 0 to 20 s Δ 0.01 s 5 s
Min Operate Time 0 to 20 s Δ 0.01 s 0 s
Follower DTL 0 to 20 s Δ 0.01 s 0 s
Reset IEC/ANSI Decaying
0 to 60 s Δ 1 s
0 s
VTS Action
8
Off
Inhibit
Non-Dir
Off
81HB2 Inhibit No
Yes
No
79 Delayed Inhibit No
Yes
No
IEC 61850 Functional Information Mapping
A51GPTOC*.Mod
Information
51G Earth Fault Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A51GPTOC*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A51GPTOC*.Health
Information
Device Healthy 0 1
A51GPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
5.18.6
Protection and Automation Functions
5.18 51G Time-Delayed Earth Fault – Measured
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 275
C53000-G7040-C014-1, Edition 11.2019