Functions > Protection > 55
VTS Inhibit Enabled
The output for the 55-1 element pickups and operation should then be mapped to the output matrix, user
logic, and communications.
Settings Menu
Functions > Function config
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
55 Power Factor Enabled
Disabled
Disabled
Functions > Protection > 55 > Gn 55-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Operation Under
Over
1Ph/3Ph Power 1Ph
3Ph
Dir. Control Non-Dir
Lead
Lag
Setting 0.05 to 0.99, Δ 0.01
Delay (DTL) 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
1 s
UC Guard No
Yes
UC Guard Setting 0.05 to 1 ⋅ I
rated
, Δ 0.05 I
rated
VTS Inhibit No
Yes
Yes
IEC 61850 Functional Information Mapping
A55PDOP*.Mod
Information
55 Power Factor Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A55PDOP*.Mod.stVal 5 5 2 1
5.21.5
5.21.6
Protection and Automation Functions
5.21 55 Power Factor
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 299
C53000-G7040-C014-1, Edition 11.2019