Siemens 7SR51 - Settings Menu; IEC 61850 Functional Information Mapping

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions > Protection > 55
VTS Inhibit Enabled
The output for the 55-1 element pickups and operation should then be mapped to the output matrix, user
logic, and communications.
Settings Menu
Functions > Function config
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
55 Power Factor Enabled
Disabled
Disabled
Functions > Protection > 55 > Gn 55-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Operation Under
Over
1Ph/3Ph Power 1Ph
3Ph
Dir. Control Non-Dir
Lead
Lag
Setting 0.05 to 0.99, Δ 0.01
Delay (DTL) 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
1 s
UC Guard No
Yes
UC Guard Setting 0.05 to 1 ⋅ I
rated
, Δ 0.05 I
rated
VTS Inhibit No
Yes
Yes
IEC 61850 Functional Information Mapping
A55PDOP*.Mod
Information
55 Power Factor Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A55PDOP*.Mod.stVal 5 5 2 1
5.21.5
5.21.6
Protection and Automation Functions
5.21 55 Power Factor
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 299
C53000-G7040-C014-1, Edition 11.2019