EasyManua.ls Logo

Siemens 7SR51 - 10.1 General Device Data

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
General Device Data
Instrumentation
Instrument Value Reference Typical Accuracy
I Current 10 % to 200 % I
rated
± 1 % or ± 1 % I
rated
V Voltage 10 % to 200 % V
rated
± 1 % or ± 1 % V
rated
W Power (P) V = V
rated
I = 10 % to 200 % I
rated
PF ≥ 0.8
± 3 % S
rated
where S
rated
= V
rated
⋅ I
rated
VA
r
Reactive power (Q)
VA Apparent power (S)
PF Power factor V = V
rated
, 10 % to 200 % I
rated
, PF ≥ 0.8 ± 0.05
f Frequency 47.5 to 52.5 Hz @ 50 Hz
57 to 63 Hz @ 60 Hz
± 10 mHz
10.1
10.1.1
Technical Data
10.1 General Device Data
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 503
C53000-G7040-C014-1, Edition 11.2019