Parameter: Setting ID
•
Default Setting: Not Active
A password required for settings changes at the device fascia Setting ID can be set in Reydisp
Manager (Configuration > Device > Settings Change Confirmation > Set).
Settings changes can only be made at the device fascia after the Setting ID code is entered.
The Setting ID will timeout 60 minutes after the last key press, or if the Control ID is entered.
Parameter: Control ID
•
Default Setting: Not Active
A password required to carry out control operations from the device fascia Control ID can be set in
Reydisp Manager (Configuration > Device > Control Confirmation > Set).
Settings changes can only be made at the device fascia after the Setting ID code is entered.
The Control ID will timeout 60 minutes after the last key press, or if the Control ID is entered.
Parameter: Reset Password
•
Default Setting: No
This function is accessible at the relay fascia only. The reset is applied to the connection password and
the maintenance password. Completion of the reset requires the Reset Confirmation ID, 0000 to
be entered.
The maintenance and connection passwords can be set and modified only through EN100 Web UI.
The passwords can also be reset from the fascia using the Reset Password feature.
The following table shows the passwords used in device EN100 for security functions.
Password
Description
Maintenance Password for:
•
EN100 firmware upgrade via Ethernet or USB
•
Firmware upgrade via Ethernet or USB
•
Setup secure engineering access – Download password-reset file
Connection Password for EN100 connection with Reydisp via Ethernet or USB
The password must contain 8 to 24 ASCII-characters and must include at least:
•
1 capital letter (A-Z)
•
1 small letter (a-z)
•
1 digit (0-9)
•
1 special character from the set !"#$%&'()*+,-/:;<=>?@[\]^_{|}~
NOTE
All passwords have no default value at device delivery and are recommended to be set by the user during
commissioning.
The passwords protect against unauthenticated access.
Settings Menu
Configuration > Device Config
Parameter Range Default Setting
System frequency 50 Hz/60 Hz 50 Hz
Active group 1, 2, 3, 4 1
3.2.5
Device Functionality
3.2 Device Configuration
56 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019