Functions > Protection > 50GS > Gn 50GS-n
Parameter Setting Options Settings
Default Gn1 Gn2 Gn3 Gn4
Setting 0.005 to 0.1 ⋅ I
rated
, Δ 0.001
I
rated
0.105 to 1 ⋅ I
rated
, Δ 0.005
I
rated
0.5 ⋅
I
rated
Delay 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
VTS Action
6
Off
Inhibit
Non-Dir
Off
79 Delayed Inhibit No
Yes
No
IEC 61850 Functional Information Mapping
A50GSPTOC*.Mod
Information
50GS Sensitive EF Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A50GSPTOC*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A50GSPTOC*.Health
Information
Device Healthy 0 1
A50GSPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
5.14.6
Protection and Automation Functions
5.14 50GS Instantaneous Sensitive Earth Fault – Measured
232 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019