EasyManua.ls Logo

Siemens 7SR51 - 10.24 59 N Neutral Voltage Displacement

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59N Neutral Voltage Displacement
Common Settings
Reference
Parameter Value
Input selection VN, VT4
Definite Time Element (59NDT)
Reference
Parameter Value
V
set
Setting 1 to 100 V
V Applied voltage (for operate time) 0 to 2 ⋅ V
set
(switched)
0 to 10 ⋅ V
set
(switched)
t
delay
Delay setting 0 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Level
Attribute
Value
V
op
Operate level V
set
: ± 2 % or ± 0.5 V
Reset level ≥ 95 % V
op
or ± 0.5 V
Repeatability ± 1 %
Variation IEC
60255-1
-10 °C to +55 °C ≤ 5 %
f
rated
± 5 % ≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time 1.5 ⋅ V
set
: 76 ms ± 20 ms
10 ⋅ V
set
: 63 ms ± 20 ms
t
op
Operate time following delay t
basic
+ t
delay
± 1 % or ± 20 ms
Repeatability ± 1 % or ± 20 ms
Overshoot time < 80 ms
Disengaging time < 100 ms
Inverse Time Element (59NIT)
Reference
Parameter
Value
Tm Time multiplier setting 0.1 to 140
V
set
Setting 1 to 100 V
10.24
10.24.1
10.24.2
10.24.3
Technical Data
10.24 59N Neutral Voltage Displacement
538 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals