EasyManua.ls Logo

Siemens 7SR51 - Settings Menu; IEC 61850 Functional Information Mapping

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[dw_7SR5_function87GHApplicationAndSettingNotes4, 1, en_US]
Figure 5-58 REF Relay Circuit
Settings Menu
Functions > Function Config
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
87GH Restricted EF Enabled
Disabled
Disabled
Functions > Protection > 87 > Gn 87GH-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Setting 0.02 to 0.95, Δ 0.005 I
rated
0.2 I
rated
Delay (DTL) 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0 s
IEC 61850 Functional Information Mapping
A87GHPTOC*.Mod
Information
87GH Restricted EF Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A87GHPTOC*.Mod.stVal 5 5 2 1
5.29.5
5.29.6
Protection and Automation Functions
5.29 87GH Restricted Earth-Fault Protection – High-Impedance
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 363
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals