[lo_7SR5_50logicdiagramAdditionalSettings, 1, en_US]
Figure 5-15
Logic Diagram: 50 Instantaneous Overcurrent – Phase (Additional Settings Using VT Inputs)
Application and Setting Notes
Parameter: Element
Default setting: Disabled
This setting is used to allow the element to be switched on and off if it is not required. A separate setting
is provided for each element. These setting can be used to select the number of elements required.
5.11.4
Protection and Automation Functions
5.11 50 Instantaneous Overcurrent – Phase
208 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019