Information
Element Phase C picked up 0 1
A50PTOC*.Str.phsC 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information
Element Phase C picked up and Fwd Direction 0 1 0
Element Phase C picked up and Rev Direction 1 0 0
A50PTOC*.Str.dirPhsC 2 1 0
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value No-Dir: 0
FWD: 1
REV: 2
Information List
Input/Output Matrix
General
Pickup
User Logic Type IEC
60870-5-1
03
DNP3 MODBUS
RTU
Inhibit 50-n Inhibit 50-n Input
50-n PhA Pickup Output
50-n PhB Pickup Output
50-n PhC Pickup Output
50-n PhA Operated Output
50-n PhB Operated Output
50-n PhC Operated Output
50-n
Pickup
50-n Pickup Output
50-n 50-n Operated Output Y Y Y
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
5.11.7
Protection and Automation Functions
5.11 50 Instantaneous Overcurrent – Phase
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 215