EasyManua.ls Logo

Siemens 7SR51 - 10.34 81 Frequency Protection - f> or f<

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
81 Frequency Protection – "f>" or "f<"
Reference
Parameter Value
f
set
Setting 43 to 68 Hz, Δ 0.01 Hz
f Applied frequency (for operate time)
Hysteresis Hysteresis 0 to 2 %, Δ 0.1 %
t
delay
Delay setting 0 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Level
Attribute Value
f
op
Operate level f
set
: ± 10 MHz
Reset level Over frequency (100 % - hysteresis) ⋅ f
op
± 10 mHz
Under frequency (100 % + hysteresis) ⋅ f
op
± 10 mHz
Repeatability ± 1 %
Variation IEC
60255-1
-10 °C to +55 °C ≤ 5 %
f
rated
± 5 % ≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic
operate time (for
ROCOF between 0.1
and 5 Hz/s)
Over frequency Typically < 110 ms
Maximum < 150 ms
Under frequency Typically < 110 ms
Maximum < 150 ms
t
op
Operate time following delay t
basic
+ t
delay
± 1 % or ± 10 ms
Repeatability ± 1 % or ± 10 ms
Disengaging time < 100 ms
10.34
Technical Data
10.34 81 Frequency Protection – "f>" or "f<"
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 549
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals