EasyManua.ls Logo

Siemens 7SR51 - Settings Menu

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Settings Menu
Functions > Control > 79 > 79 Common
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Autoreclose Enabled
Disabled
Disabled
Number of Shots 1 to 4 1
Retry Enable Enabled
Disabled
Disabled
Retry Attempts 1 to 10 1
Retry Interval 0 to 600 s Δ 1 s 60 s
Reclose Blocked Delay 0 to 600 s Δ 1 s 60 s
Sequence Fail Timer 0 to 600 s Δ 1 s 60 s
Sequence Co-ord Enabled
Disabled
Cold Load Action Off
Delayed
Functions > Control > 79 > 79PF
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
PF Triggers <all>
50-n
51-n
<all>
PF Trips to LO Target 1 to 5 5
PF Deadtime 1 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
PF Deadtime 2 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
PF Deadtime 3 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
Delayed
5 s
PF Deadtime 4 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
5 s
PF Protection Trip 1 Inst
Delayed
Inst
7.3.5
Control Functions
7.3 79 Automatic Reclosing
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 433
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals