IEC 61850 Functional Information Mapping
Functional Description Logical Device LD Logical Node LN Instantiated Data Object
DOI
47-(Gn) PROT A47PTOV(Gn) Mod
Beh
Health
NamPlt
Str
Op
A47PTOV*.Mod
Information
47 Sequence Voltage Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A47PTOV*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A47PTOV*.Health
Information
Device Healthy 0 1
A47PTOV*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A47PTOV*.Op
Information
Element Operated 0 1
A47PTOV*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0