The LED and binary outputs can also be reset via the communications or a binary input.
See 3.5 Binary Outputs .
Control of Data Storage
The device allows the user to reset the data storage functions from the fascia menu. Reset is initiated from the
setting menu by selecting the appropriate parameter and using the arrows to select Yes. Select Enter to
confirm the action. The following items can be reset by this method:
Demand Reset
Clear Waveforms
Clear Faults
Clear Events
A waveform storage can also be triggered from the setting menu by selecting the appropriate parameter using
the arrows to select Yes and selecting Enter to confirm the action.
i
i
NOTE
If a setting ID is active this will be required to be entered to make the selection.
These items can also be reset over the communications protocol.
These items can also be reset from a binary input or by creating a reset logic in the Reylogic tool.
i
i
NOTE
The controlling action may be restricted by the devices operating mode which is managed in junction with
the device operating mode parameters, (see 3.2 Device Configuration ).
See 3.6 Data Storage .
IEC 61850 Functional Information Mapping
Control LLN0 (CTRL/LLN0)
LLN0.Mod
Information
Device Ready 0 1 1
Out Of Service Mode x 1 0
LLN0.Mod.stVal 5 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
7.1.3
Control Functions
7.1 Device Control Functions
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 401
C53000-G7040-C014-1, Edition 11.2019