GS In/Out
•
Operate Mode:
– Set L or R mode
– Set L mode
– Set R mode
•
79 Out of Service/In Service
•
Hotline Working In/Out
•
Inst Prot’n In/Out
•
79 Trip and Reclose Confirm Action
•
79 Trip & Lockout Confirm Action
NOTE
If the function is disabled the control operation will be blocked or removed from the options.
See 3.1 Device Fascia .
Settings > Configuration > Device Menu
The following are controllable items in the Device menu:
•
Active group
•
Time source
•
Operating mode
•
Setting ID
•
Control ID
•
Passwords reset
See 3.2 Device Configuration .
Control from Binary Inputs
When energized the binary inputs can be used for selected control functionality:
•
Select device local/remote/out of service operating modes
•
Inhibit operation of function elements
•
Reset counters and meters
•
Initiate operation of associated circuit‑breaker open/close
•
Trigger data storage functions
•
Initiate Control Mode menu functions
See 3.4 Binary Inputs .
Control of Binary Outputs
To clear any latched LED’s or binary output relays the Right arrow must be held for 3 seconds when the Home
Screen is visible.
NOTE
This can be carried out without entering a User ID.
Control Functions
7.1 Device Control Functions
400 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019