Table 7-1 Points List
User Logic IEC 60870-5-1 03 DNP3 Modbus
User mimic status 1 (to
10)
N N N
User SP serial command 1
(to 8) (On/Close)
Y Y Y
User DP serial command 1
(to 8) (On/Close)
Y Y Y
User DP serial command 1
(to 8) (Off/Open)
Y Y Y
The operating mode of the controllable in IEC 61850s can be selected with the appropriate control model.
3 different control model types are available:
•
Direct without feedback monitoring (direct w. normal secur)
•
Direct with feedback monitoring (direct w. enh. security)
•
With SBO with feedback monitoring (SBO w. enh. security)
NOTE
SBO without feedback monitoring is not supported.
The Control Confirmation ID, when active, must be entered to proceed with the control action. If any
logic interlocking has been created within the Reylogic the item may not change state and the operation
blocked.
Control from Control Mode Menu/Fascia Function Keys
The device provides a number of preconfigured control items from the fascia menus. From the Home Screen
the Down arrow can be pressed to access the Main Menu. The user can then, using the arrows, scroll to the
Control Mode menu. The Right arrow is used to enter the Control Mode menu.
[sc_7SR5_ControlModeMenu, 1, --_--]
Figure 7-1 Control Mode Menu
The following items are available as preconfigured controllable items located in the Control Mode menu:
•
CB Open/Close
•
EF In/Out
Control Functions
7.1 Device Control Functions
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 399