IEC 61850 Functional Information Mapping
A50AFDSARC*.Mod
Information
Reset Device x
A50AFDSARC*.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A50AFDSARC*.Health
Information
Device Healthy 0 1
A50AFDSARC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A50AFDSARC*.FACntRs
Information
Measurand Value
AFD Operate Count A50AFDSARC*.FACntRs.stVal 0 to 10000
Information
AFD Operate Count Value (0 to 10000)
A50AFDSARC*.FACntRs.ctlVal Value (0 to 10000)
A50AFDSARC*.FADet
Information
AFD Operated 0 1
A50AFDSARC*.FADet.stVal 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
5.12.6
Protection and Automation Functions
5.12 50AFD Arc Flash Detection
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 219