Device Control Functions
Overview of Functions
7SR5 devices include several types of control functionality.
Structure of the Function
7SR5 devices include several types of control functionality. Control is divided into the following categories:
Device fascia LCD mimic diagram(s)/fascia function keys
Control Mode menu/fascia function keys
Settings > Configuration > Device menu
Binary inputs
Reset of binary outputs
Control of data storage functions
Single point data points
Double point data points
Settings > Functions > Control menu
Control from Device Fascia LCD Mimic Diagram(s)/Fascia Function Keys
Device Fascia LCD Mimic Diagram
Controllable plant items that have been included by the user in the configurable fascia LCD, (see 3.1 Device
Fascia ).
The device is supplied with a default Home Screen displaying the basic metered values. Up to 5 screens,
including the default, can be configured in the Reydisp PC tool and sent to the device. The screens support
user configurations for meters, mimic indications and controllable items.
All controllable mimic items are select before execute from the fascia.
From the selected screen the Enter key should be used to access the controllable item. If no controllable
items are configured the device will display a message to advise the user.
i
i
NOTE
During device configuration plant items may be configured to display position only or as controllable items.
The display will flash the first controllable item on the chosen screen. Using the arrow keys the user must navi-
gate to select the correct item. Once selected the item will flash. The item can then be controlled using the I
and O keys to select the correct operation. The Enter key is used to confirm the action and generates the
control command.
i
i
NOTE
The controlling action may be restricted by the devices operating mode which is managed in junction with
the device operating mode parameters, (see 3.2 Device Configuration ).
User Controls
To support the control of additional user configured items the device provides a number of control elements
that can be used in the user logic, mimic diagram and communication interface configuration.
7.1
7.1.1
7.1.2
Control Functions
7.1 Device Control Functions
398 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals