Functions > Protection > 59 > Gn 59 Common
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Input Selection Ph-Ph
Ph-N
Ph-Ph
Functions > Protection > 59 > Gn 59-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Pickup Option Any
All
Any
Setting 1 to 200 V, Δ 0.5 V 80 V
Hysteresis 0 to 80 %, Δ 1 % 3 %
Delay 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0.1 s
VTS Inhibit No
Yes
No
IEC 61850 Functional Information Mapping
A59PTOV*.Mod
Information
59 Overvoltage Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A59PTOV*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A59PTOV*.Health
Information
Device Healthy 0 1
A59PTOV*.Health.stVal 3 1
5.22.6
Protection and Automation Functions
5.22 59 Overvoltage Protection – 3 Phase
310 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual