Settings Menu
Functions > Protection > 60VTS
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Component NPS
ZPS
NPS
V 7 to 110 V, Δ 1 V 7 V
I 0.05 to 1 ⋅ I
rated
, Δ 0.05 ⋅ I
rated
0.1 ⋅
I
rated
V
PPS
15 to 110 V, Δ 1 V 15 V
I
PPS
Load 0.05 to1 ⋅ I
rated
, Δ 0.05 ⋅ I
rated
0.1 ⋅
I
rated
I
PPS
Fault 0.05 to 20 ⋅ I
rated
, Δ 0.05 ⋅
I
rated
10 ⋅ I
rated
Delay (DTL) 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
10 s
Information List
Input/Output Matrix
General
Pickup
User Logic Type Serial
Protocol
Inhibit 60VTS Inhibit 60VTS Input
60VTS 60VTS Operated Output Y
60VTS Pickup Output
The complete serial protocol information list containing the DNP3, IEC 60870-5-103, and Modbus RTU data
information for the configured device can be generated using the Export Report feature in the Reydisp
Manager 2 tool, Serial Comms & Events.
6.3.5
6.3.6
Supervision Functions
6.3 60VTS VT Supervision
382 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019