EasyManua.ls Logo

Siemens 7SR51 - 10.17 50 N Instantaneous Earth Fault - Calculated

Siemens 7SR51
556 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
50N Instantaneous Earth Fault – Calculated
Reference
Parameter Value
Directional control
13
Non-Dir, forward, reverse
I
set
Setting 0.05 to 2.5 ⋅ I
rated
, Δ 0.01
2.55 to 25 ⋅ I
rated
, Δ 0.05
25.5 to 50 ⋅ I
rated
, Δ 0.5
I Applied current (for operate time) 0 to 2 ⋅ I
set
(switched)
0 to 5 ⋅ I
set
(switched)
t
delay
Delay setting 0 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Level
Attribute Value
I
op
Operate level I
set
: ± 5 % or ± 1 % I
rated
Reset level ≥ 95 % I
op
Repeatability ± 1 %
Transient overreach (X/R ≤ 100) ≤ -5 %
Variation IEC
60255-1
-10 °C to +55 °C ≤ 5 %
f
rated
± 5 % ≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time 2 ⋅ I
set
: 40 ms ± 10 ms
5 ⋅ I
set
: 30 ms ± 10 ms
t
op
Operate time following delay t
basic
+ t
delay
± 1 % or ± 10 ms
Repeatability ± 1 % or ± 10 ms
Overshoot time < 40 ms
Disengaging time < 50 ms
10.17
13
Requires VT inputs
Technical Data
10.17 50N Instantaneous Earth Fault – Calculated
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 527
C53000-G7040-C014-1, Edition 11.2019

Table of Contents

Related product manuals