Where the power phasor is within the power range (in tripping zone defined by Power Type, Direction
and Operate Mode), an output is given.
The setting for all power types is in rated apparent power (S
rated
), where:
rated (nominal) 3 phase power =
Settings Menu
Functions > Function Config
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
32 Power Enabled
Disabled
Disabled
Functions > Protection > 32 > Gn 32-n
Parameter Range Settings
Default Gn1 Gn2 Gn3 Gn4
Element Enabled
Disabled
Disabled
Operation Under
Over
Over
1Ph/3Ph Power 1Ph
3Ph
3Ph
Power Real (P)
Reactive (Q)
Apparent (S)
Real
Dir.Control Non-Dir
Forward
Reverse
Non-Dir
Setting 0.05 to 2 ⋅ S
rated
, Δ 0.01 S
rated
1 ⋅ S
rated
Delay 0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
1 s
VTS Inhibit No
Yes
No
UC Guard No
Yes
No
UC Guard Setting 0.05 to 1 ⋅ I
rated
, Δ 0.05 I
rated
0.2 ⋅
I
rated
IEC 61850 Functional Information Mapping
A32PDOP*.Mod
Information
32 Power Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
5.4.5
5.4.6
Protection and Automation Functions
5.4 32 Power Protection
166 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019