Information
Element Inhibited x x 1 0
A32PDOP*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A32PDOP*.Health
Information
Device Healthy 0 1
A32PDOP*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A32PDOP*.Op
Information
Element Operated 0 1
A32PDOP*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A32PDOP*.Str
Information
Element Phase A picked up or 0 1
Element Phase B picked up or 0 1
Element Phase C picked up 0 1
A32PDOP*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Protection and Automation Functions
5.4 32 Power Protection
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 167
C53000-G7040-C014-1, Edition 11.2019