Functions > Protection > 49 > Gn 49-n
Parameter Setting Options Settings
Default Gn1 Gn2 Gn3 Gn4
Char IEC
User
IEC
Time Constant 1 to 1000 min, Δ 0.5 min 10 min
Capacity Alarm Disabled
Enabled
Disabled
Capacity Alarm Setting 50 to 100 %, Δ 1 % 50 %
IEC 61850 Functional Information Mapping
A49PTTR*.Mod
Information
49 Thermal Overload Enabled (Function Config) x 0 1 1
Element Disabled 1 x 0 0
Element Inhibited x x 1 0
A49PTTR*.Mod.stVal 5 5 2 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A49PTTR*.Health
Information
Device Healthy 0 1
A49PTTR*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A49PTTR*.Op
Information
Element Operated 0 1
A49PTTR*.Op.general 0 1
5.10.6
Protection and Automation Functions
5.10 49 Thermal Overload Protection
204 Reyrolle 7SR5, Overcurrent Protection Device, Device Manual
C53000-G7040-C014-1, Edition 11.2019