Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A50NPTOC*.Health
Information
Device Healthy 0 1
A50NPTOC*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A50NPTOC*.Op
Information
Element Operated 0 1
A50NPTOC*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A50NPTOC*.Str
Information
Element picked up 0 1
A50NPTOC*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information
Element picked up and Fwd Direction 0 1 0
Element picked up and Rev Direction 1 0 0
A50NPTOC*.Str.dirGeneral 2 1 0
Protection and Automation Functions
5.15 50N Instantaneous Earth Fault – Calculated
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 239
C53000-G7040-C014-1, Edition 11.2019