A55PDUP*.Health
Information
Device Healthy 0 1
A55PDUP*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
A55PDUP*.Op
Information
Element Operated 0 1
A55PDUP*.Op.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
A55PDUP*.Str
Information
Element Phase A picked up or 0 1
Element Phase B picked up or 0 1
Element Phase C picked up 0 1
A55PDUP*.Str.general 0 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value TRUE: 1
FALSE: 0
Information
Element Phase A picked
up and Fwd Direction
x 1 1 0 0 0 0 1 0 0 1 0
Element Phase A picked
up and Rev Direction
x x x 1 0 0 1 0 0 0 0 0
Element Phase B picked
up and Fwd Direction
x x x 0 0 0 0 1 0 1 0 0
Element Phase B picked
up and Rev Direction
1 x 1 1 0 1 0 0 0 0 0 0
Element Phase C picked
up and Fwd Direction
1 x x 0 0 0 0 1 1 0 0 0
Element Phase C picked
up and Rev Direction
x 1 x 1 1 0 0 0 0 0 0 0
A55PDUP*.Str.dirGen-
eral
3 3 3 2 2 2 2 1 1 1 1 0
Protection and Automation Functions
5.21 55 Power Factor
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 303
C53000-G7040-C014-1, Edition 11.2019

Table of Contents