Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value ON: 1
OFF: 0
Information
DPDONS Status (Off/Open) 0 1 0 1
DPDONS Status (On/Closed) 0 0 1 1
DPDONSGGIO*.DPCSO.stVal 00 01 10 11
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value ON: 1
OFF: 0
User Double Point GGIO Control Elements (Enhanced Security) (DPDOesGGIO1, DPDOesGGIO2, DPDOesGGIO3,
DPDOesGGIO4)
DPDOESGGIO*.Mod
Information
Reset Device x
DPDOESGGIO*.Mod.stVal 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
DPDOESGGIO*.Health
Information
Device Healthy 0 1
DPDOESGGIO*.Health.stVal 3 1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value OK: 1
WARNING: 2
ALARM: 3
Control Functions
7.1 Device Control Functions
Reyrolle 7SR5, Overcurrent Protection Device, Device Manual 407
C53000-G7040-C014-1, Edition 11.2019